Magnetic Properties

powercore®

thyssenkrupp Electrical Steel’s high-tech core material powercore® has been largely responsible for increasing the efficiency of power and distribution transformers.

The use of powercore® can also significantly reduce total manufacturing costs for transformers, a major advantage in the face of rising raw material costs.

powercore® is the core material for the future!

Cost benefits due to:
  • lower core weights
  • more compact dimensions
Higher energy efficiency due to:
  • minimum no-load losses
  • better capitalization of losses
Reduced noise emissions due to:
  • optimized magnetic domain structure
  • improved insulation properties
THICKNESSMAXIMUM SPECIFIC LOSS ATMINIMUM POLARIZATION
Grademminch1.7T 50Hz W/kg1.7T 60Hz W/kg800 A/m T
23HP80d0.230.010.801.041.85
23HP85d0.230.010.851.121.85
23HP90d0.230.010.901.191.85
23HP95d0.230.010.951.251.85
23HP100d0.230.011.001.321.85
23CG1100.230.011.101.451.78
23CG1200.230.011.201.571.78
23CG1270.230.011.271.651.75
27HP90d0.270.010.901.191.85
27HP95d0.270.010.951.251.85
27HP1000.270.011.001.321.88
27HP1100.270.011.101.451.88
27CG1200.270.011.201.581.78
27CG1300.270.011.301.681.78
27CG1400.270.011.401.751.75
(d) = Magnetic domain refined by laser scribing.
All the grades may be delivered with laser domain refinement if not agreed otherwise. Magnetic properties measured by Epstein frame or by SST as defined in IS 649.